Installing the Chassis Intrusion Detection switch
Procedure
1. If installed, remove the front bezel.
2. Power down the server.
3. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
4. Disconnect all peripheral cables from the server.
5. If the full-length GPU is installed on the secondary riser cage, remove the secondary riser cage.
6. Remove the air baffle.
7. Attach the Chassis Intrusion Detection switch to the chassis, connect the cable to the system board,
and then route the cable as shown in following illustration.
8. If removed, install the secondary riser cage.
9. Install the air baffle.
10. Install the access panel.
11. Install the server into the rack.
12. Connect all peripheral cables to the server.
13. Connect each power cord to the server.
14. Connect each power cord to the power source.
15. Power up the server on page 43.
16. If removed, install the front bezel.
The installation is complete.
116 Hardware options installation