Shenzhen Hpmont Technology Co., Ltd Appendix A Parameters
HD30 Series Inverters User Manual 155
No. Name Range
Factory
Default
Unit
Modified
attributes
Setting
F09.00
V/f curve selection of
motor 1
0: Line
1: Square curve
2: 1.2 exponential curve
3: 1.7 exponential curve
4: User-defined curve
0 1 ×
F09.01
V/f frequency value F3
of motor 1
F09.03F08.03 0.00Hz 0.01Hz ×
F09.02
V/f voltage value V3 of
motor 1
F09.04F08.01 0V 1V ×
F09.03
V/f frequency value F2
of motor 1
F09.05F09.01 0.00Hz 0.01Hz ×
F09.04
V/f voltage value V2 of
motor 1
F09.06F09.02 0V 1V ×
F09.05
V/f frequency value F1
of motor 1
0.00F09.03 0.00Hz 0.01Hz ×
F09.06
V/f voltage value V1 of
motor 1
0F09.04 0V 1V ×
F09.07
Torque boost of motor
1
0.030.0%
0.0: Auto torque boost
45kW and
below: 2.0%
55132kW
inverter:
1.0%
160kW and
above:
0.5%
0.1% ×
F09.08
Cut-off point used for
manual torque boost of
motor 1
0.050.0% (F08.03) 30.0% 0.1%
F09.09
Slip compensation gain
of motor 1
0.0300.0% 100.0% 0.1%
F09.10
Slip compensation filter
time of motor 1
0.0110.00s 0.10s 0.01s
F09.11
Slip compensation
limitation of motor 1
0.0250.0% 200.0% 0.1% ×
F09.12
Compensation
constant of motor 1
0.125.0s 2.0s 0.1s
F09.13 Reserved
F09.14
AVR function of motor
1
0: Disabled
1: Enabled all the time
2: Disabled in deceleration
process
1 1
F09.15
Oscillation-suppression
mode of motor 1
0: Oscillation suppression is
dependent on the motor’s
exciting current component
1 1
A