Shenzhen Hpmont Technology Co., Ltd Appendix A Parameters
HD30 Series Inverters User Manual -167-
No. Name Range
Factory
Default
Unit
Modified
attributes
Setting
F17.00 Data format
0: 1-8-2 format, no parity,
RTU
1: 1-8-1 format, even
parity,RTU
2: 1-8-1 format, odd parity,
RTU
3: 1-7-2 format, no parity,
ASCII
4: 1-7-1 format, even parity,
ASCII
5: 1-7-1 format, odd parity,
ASCII
0 1 ×
F17.01 Baud rate selection
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
5: 38400bps
6:57600bps
7:76800bps
8:115200bps
3 1 ×
F17.02 Local address 0-247 2 1 ×
F17.03 Host PC response time 0-1000ms 0ms 1ms ×
F17.04
Time threshold for
detecting
communication status
0.0-1000.0s
When F17.04 = 0, it will not
detect communication time
out.
0.0s 0.1s ×
F17.05
Detecting time at
communication error
0.0-1000.0s
When F17.05 = 0, it will not
detect the communication
error.
0.0s 0.1s ×
F17.06
Action selection at
communication time
out
0: Coast to stop
1: Emergency stop
2: Decelerate to stop
3: Continue to run
3 1 ×
F17.07
Action selection at
communication fault
3 1 ×
F17.08
Action selection at
communication
peripheral device fault
1 1 ×
F17.09
Communication write
function parameter of
storage EEPROM
method selection
0: Communication write
function parameter without
storage EEPROM.
1: Communication write
function parameter with
storage EEPROM.
1 1 ×
Group F18 Display Control Parameters (refer to pages 107
109)
A