Shenzhen Hpmont Technology Co., Ltd Appendix A Parameters
HD30 Series Inverters User Manual -175-
No. Name Range
Factory
Default
Unit
Modified
attributes
Setting
feedback out of the
limit
When set to 0, does not
detect PID feedback out of
the limit
F20.18 Auto reset times
0-100
0: No auto reset function
0 1 ×
F20.19 Auto reset interval 2.0-20.0s/times 5.0s/ times
0.1s/
times
×
F20.20
Faulted relay action
selection
Units: In auto reset process
0: Faulted relay doesn’t act
1: Faulted relay acts
Tens: In the undervoltage
process
0: Faulted relay doesn’t act
1: Faulted relay acts
00 1 ○
F20.21
Type of fifth latest (the
last) fault
0: No fault history
E0001: Acc. overcurrent
E0002: Dec. overcurrent
E0003: Costant overcurrent
E0004: Acc. overvoltage
E0005: Dec. overvoltage
E0006: Constant overvoltage
E0007: Stall overvoltage
E0008: Fault of power
module
E0009: Heatsink overheat
E0010: Fault of braking unit
E0011: CPUfault
E0012: Parameters
auto-tuning fault
E0013: Contactor is not
actuated
E0014: Fault of current
detection circuit
E0015: Fault of input phase
E0016: Fault of output phase
E0017: Inverter overload
E0018: Inverter output is
unloaded
E0019: Motor overload
E0020: Motor overheat
E0021: Access fault of
Control board EEPROM
E0022: Access fault of
display panel EEPROM (only
displaying without any
protection)
0 1 *
A