EasyManuals Logo

hpmont HD30 Series User Manual

hpmont HD30 Series
215 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #210 background imageLoading...
Page #210 background image
Shenzhen Hpmont Technology Co., Ltd Appendix C Communication Protocol
HD30 Series Inverters User Manual 193
8. Special instruction
1) For the data frame in ASCII mode, if the frame length is an even number, the frame is
abandoned.
2) Group F08 (Asynchronous motor 1 parameter setting), Group F12 (Reserved), F13.00
F13.15 (Asynchronous motor 2 parameter setting) and Group F17 (SCI communication
parameters) are the inverter parameter which can be read but cannot be modified by the host
computer.
3) F01.00 (user password) cannot be set and adjusted through communication as well, but the
user can verify the user password by writing F01.00 and get access to adjust inverter function
parameters on the host. After adjustment, the user can close the permission by writing invalid
password to F01.00.
4) If many multi-function input terminals are set the same function, it may cause dysfunction.
Therefore, the user should avoid this case when modify the multi-function terminal function via
the MODBUS.
C

Table of Contents

Other manuals for hpmont HD30 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the hpmont HD30 Series and is the answer not in the manual?

hpmont HD30 Series Specifications

General IconGeneral
Brandhpmont
ModelHD30 Series
CategoryInverter
LanguageEnglish

Related product manuals