Step 4 Remove the disc nut from the lter, remove the lter.
Step 5 Block the inlet and outlet of the water pump.
NO TICE
Before removing the water pump, block the water inlet pipe and drainpipe of
the water pump to prevent water
overowing out of the water pan and water
pipe.
At the front end of the water pump, block the drain outlet (shown in Figure
4-35) of the water pan using a proper object, such as a cloth based on the
actual condition.
At the rear end of the water pump, bend the white drainpipe (shown in Figure
4-36) and tie it securely using a proper object, such as a cable tie or rope based
on the actual condition.
Figure 4-35 Water pan hole
(1) Water pan hole
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 4 Parts Replacement
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 92