Figure 4-36 Water pump drainpipe
(1) Water pump drainpipe
Step 6 Use a at-head screwdriver to remove the two hose clamps from the pipe, and
remove the hoses at the water inlet and outlet of the condensate pump, as shown
in Figure 4-37.
Figure 4-37 Removing hose clamps from a pipe
Step 7 Use a socket wrench to remove the two M6 screws from the sheet metal fastener
of the water pump, and pull out the water pump assembly, as shown in Figure
4-38.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 4 Parts Replacement