FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
3 Hardware Installation
Copyright © Huawei Technologies Co., Ltd.
41
Set the removed materials aside for they will be used in subsequent installation steps.
Figure 3-17 Removing an aisle side sealing plate from the Converged Cabinet
Step 2 Remove the other aisle side sealing plate in the same way.
Step 3 Secure the sealing plate fasteners to the aisle frame on the end cabinet using M5 tapping
screws, as shown in Figure 3-18.