IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
6 Emergency Operations
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
154
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.
6.5 Emergency Operations for Overtemperature
Prerequisites
The IDS1000 is experiencing overtemperature or an overtemperature alarm is generated.
Procedure
Step 1 Locate the high-temperature area.
Step 2 Measure the actual ambient temperature using a thermometer.
Step 3 Check whether the actual temperature exceeds the designed normal range.
If no, check whether the T/H sensor is faulty, and replace by following instructions in 5.3.1
Replacing a T/H Sensor if it is faulty.
If yes, go to Step 4.
Step 4 Lower the temperature in the area.
Step 5 For details, see 4.9 Temperature Alarms.
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.
6.6 Emergency Operations for the Management System
Communication Failure
Prerequisites
The management system communication is interrupted.
Before the management system communication is restored, the management system cannot
perform real-time monitoring for the IDS1000 data center. Add people to perform preventive
maintenance inspection in related areas.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei IDS1000-A and is the answer not in the manual?

Huawei IDS1000-A Specifications

General IconGeneral
BrandHuawei
ModelIDS1000-A
CategoryStorage
LanguageEnglish

Related product manuals