IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
5 Parts Replacement
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
110
Figure 5-27 Installing an RH2288 V2 server
Step 5 Reconnect the cables and the power plug.
Step 6 Press the power switch on the front panel of the RH2288 V2 server to power on the server,
and check that the RH2288 V2 server is working properly.
If the server indicator is green, the server is working properly.
Step 7 Configure the server by referring to the management system initial configuration guide.
----End
Follow-up Procedure
Dispose of the removed RH2288 V2 server that is confirmed faulty.
5.3.13 Replacing Access Control Components
5.3.13.1 Replacing a Card Reader
Prerequisites
A card reader needs to be replaced.
A spare card reader of the same model is available and functional.
Impact on the System
None
Preparations
Tools: adjustable wrench, Phillips screwdriver, protective gloves
Material: spare access card and card reader