IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
5 Parts Replacement
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
82
Figure 5-6 Installing screws a the upper and lower sides of the rPDU
Step 9 Connect the rPDU power cable on the top of the cabinet.
Step 10 Switch on the circuit breaker for the rPDU in the PDC and check that the new rPDU is
working properly.
Step 11 Insert device power plugs in the rPDU.
Step 12 Reinstall the cabinet top baffle plate.
----End
Follow-up Procedure
Dispose of the removed rPDU that is confirmed faulty.
5.2 Replacing Cooling System Components
5.2.1 Replacing a Remote T/H Sensor for an Air Conditioner
Prerequisites
A remote T/H sensor needs to be replaced.
A spare T/H sensor of the same model is available and functional.
Impact on the System
None