IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
5 Parts Replacement
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
87
Install air filters as instructed by the labels to avoid reverse installation.
Step 5 Choose Maint > Performance Maint on the home screen and clear the air filter running
time.
----End
Follow-up Procedure
Dispose of the removed air filter that is confirmed faulty.
5.2.4 Replacing Parts of an Air-Cooled Precision Air Conditioner
For the detailed parts replacement procedures for an air-cooled precision air conditioner,
see documents delivered with the air conditioner.
During air conditioner parts replacement, the air conditioner may need to be powered off.
Take measures to prevent device overheating.
Table 5-1 and Table 5-2 list the parts that can be replaced for an air-cooled precision air
conditioner.
Table 5-1 Parts that can be replaced for a 20 kW precision air conditioner
No.
Item
1
Air filter
2
Indoor fan
3
Compressor
4
Humidifier cylinder
5
Electric heater
6
Solenoid valve coil
7
Components inside the control box, including the main control board, circuit
breaker, AC contactor, transformer, fuse, fuse base, and so on
8
Air intake and exhaust temperature sensors
9
T/H sensor
10
Rectifier
11
Float

Table of Contents