IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
3 Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
39
Semi-annual maintenance of the fire extinguishing system involves system commissioning.
Before the maintenance, inform the related administrative departments that the fire
extinguishing system will be maintained and stop working. In addition, disable the logical
control function of the area or system to prevent false alarms.
Before maintaining the system, ensure that all control cables to solenoid valve drivers have
been disconnected. This prevents the agent release due to misoperations, and prevents
accidental damage. After the maintenance is complete, reconnect the solenoid valves and
inform the administrative departments that the fire extinguishing system has become
operational.
Table 3-18 Semi-annual maintenance checklist for the fire extinguishing system
Item
Method
Expected Result
Troubleshooting
Fire
extinguishi
ng system
Commission the
fire extinguishing
system by
following the
instructions in the
commissioning
guide in use.
Components work
properly, and the
management system
displays related
alarms.
Replace faulty components
by following instructions in
5.4 Replacing Fire
Extinguishing System
Components (Standard).
Emergency
abort button
Check the
emergency abort
button.
The switch and panel
are intact.
If the switch is damaged,
replace it by following
instructions in 5.5.6
Replacing the Emergency
Abort Button.
Heat
detector
Heat the heat
detector using a
heating device.
If the temperature
exceeds the alarm
threshold, the alarm
indicator is steady on.
If the fault persists, replace
the heat detector by following
instructions in 5.5.2
Replacing a Heat Detector.
Smoke
detector
Release smoke
onto the smoke
detector using a
smoke pistol.
If the smoke density
exceeds the alarm
threshold, the alarm
indicator is steady on.
If the fault persists, replace
the smoke detector by
following instructions in 5.5.1
Replacing a Smoke Detector.
VESDA
Check the VESDA
sampling pipe.
The supports and
connectors of the
sampling pipe are
securely connected.
Connect the supports and
connectors of the sampling
pipe securely.
Completely close
or open the
sampling pipe.
An alarm is
generated.
See documents delivered with
the VESDA.
Release smoke to
the furthest end of
the VESDA
The VESDA
generates an alarm in
120s.
See documents delivered with
the VESDA.