IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
4 Alarms and Faults
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
71
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooting
Major
The compressor
generates a loud
noise.
The sheet metal
for securing the
compressor
during
transportation
is not removed.
Remove the sheet metal
and check whether the
abnormality disappears.
The compressor
starts and stops
at short
intervals.
Troubleshoot by
following instructions
in Comp HP switch,
and check whether the
abnormality disappears.
The compressor
suffers from
liquid strike.
Contact Huawei
technical support.
Major
An indoor fan does
not work.
A fan alarm is
generated.
Check whether an
alarm is generated. If
yes, handle the alarm
by referring to the
alarm reference list.
The fan does
not need to
work.
Choose Running >
Status on the controller
home screen and check
the indoor fan control
status. If the control
status is 0%, the fan
does not need to work,
and there is no fault. If
the control status is
greater than 0%, the fan
is faulty and needs to be
rectified.
The switch of
the indoor fan
is not turned
on.
Turn on the switch, and
check whether the
abnormality disappears.