Table 3. Firmware Error Codes. (continued)
Error Code Description Action / Possible Failing FRU
4011 2061 A high -12 voltage was detected
1. If a location code is displayed with
this error code, replace the part at
that location.
2. Replace the power supplies
one-at-a-time.
Location: P3-V1
Location: P3-V2
Location: P3-V3
3. Replace the system board.
Location: P1
(See note 3 on page 115.)
40112062 Low 1.8 V reading detected.
1. If a location code is displayed with
this error code, replace the part at
that location.
2. Replace the power supplies
one-at-a-time.
Location: P3-V1
Location: P3-V2
Location: P3-V3
3. Replace the processor cards.
Location: P1-C1
Location: P1-C2
40112063 Critically low 1.8 V reading detected
1. If a location code is displayed with
this error code, replace the part at
that location.
2. Replace the power supplies
one-at-a-time.
Location: P3-V1
Location: P3-V2
Location: P3-V3
3. Replace the processor cards.
Location: P1-C1
Location: P1-C2
40112064 Critically high 1.8 V reading detected
1. Replace the power supplies
one-at-a-time.
Location: P3-V1
Location: P3-V2
Location: P3-V3
2. Replace the processor cards.
Location: P1-C1
Location: P1-C2
154 Service Guide