NeoGCP i7 PLUS+
- 17 -
Number [15] ~ Number [24] DI-CONFIG 5.6.
- When Vdcā is input through ports [15] - [24], corresponding signal will be as shown below.
- For details of DI, refer to [DI 09 SET].
< DI Wiring Diagram >
Number [25] ~ Number [40] DO-CONFIG 5.7.
- Output signal set by user will transmit through ports [25] ~ [40].
- Capacity of RELAY 1 ~ RELAY 8 is 250[Vac], 24[Vdc], MAX 5[A].
- When using external relay, please consider relay capacity.
- For details of DO, refer to [DO 10 Set].
< DO Wiring Pattern Diagram >
Number [41] ~ Number [46] Sensor Input 5.8.
- Common of sensors will be input by port [41].
- Fuel level sensor of 4~20 [mA] will be input by port [42].
- User temp sensor will be input by port [43].
- RTD type Oil sensor will be input by port [44].
- RTD type Oil press sensor will be input by port [45].
- RTD type Coolant temp sensor will be input by port [46].