NeoGCP i7 PLUS+
- 34 -
COOLANT TEMP S/W 9.5.
- Used as coolant switch contact.
- When contact is input, operation mode of Gen-set will switch according to set alarm level after set delay
time.
- If coolant high temp occurs in [BUILD-UP] or [RUN] or [COOLDOWN], then [F_COOLANT TEMP HIGH]
Alarm will output.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level)
OIL PRESS S/W 9.6.
- Used as oil press switch contact.
- When contact is input, operation mode of Gen-set will switch according to set warning level after set
delay time.
- If Coolant High Temp occurs in [BUILD-UP] or [RUN] or [COOLDOWN], then [F_OIL PRESS LOW] Alarm
will output.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level)
COOLANT LEVEL S/W 9.7.
- Used as coolant level switch contact.
- When contact is input, operation mode of Gen-set will switch according to set Alarm level after set delay
time.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level)
NO CHARGING S/W 9.8.
- Used as battery charging failure contact.
- When contact is input, operation mode of Gen-set will switch according to set warning level after set
delay time.
- Only detects in [RUN] .
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level)
FAIL TO START 9.9.
- Used as start failure contact.
- When contact is input, operation mode of Gen-set will switch according to set warning level after set
delay time.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level)