Waiting time for RPM to fall within rated
range
Setup cooldown time in AUTO Mode
[C_AIR HEATER] setup of use/not use and
operation method
Not use,
sensor, switch,
sensor+switch
[C_AIR HEATER] output in temp lower than
set value
[C_AIR HEATER] output holding time
12. PROTECTION
- Setup of Protection during Running or Stop.
- Setup impossible during running.
- In case of OVR, OCR, and OCGR, Constant and Inverse will operate at the same time.
Duplicate operation in Instant setup.
Start from over voltage
level
Start from over voltage
level
Refer to Inverse Characteristics
Curve
Start from 130% of rated
voltage
Within 200ms
(The higher the input voltage, time
will decrease)
Start from over current
level
Start from over current
level
Refer to Inverse Characteristics
Curve
Start from 200% of rated
current
Within 200ms
(The higher the input current, time
will decrease)
Start from ground over
current level
Start from ground over
current level
Refer to Inverse Characteristics
Curve
Start from 200% of ground
current level
Within 200ms
(The higher the input current, time
will decrease)