REV. N
NeoGCP i7 PLUS+
- 35 -
FAIL TO STOP 9.10.
- Used as stop failure contact.
- When contact is input, operation mode of Gen-set will switch according to set warning level after set
delay time.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level)
BUILD-UP EXPIRE 9.11.
- Used as fail to build-up contact.
- When contact is input, operation mode of Gen-set will switch according to set warning level after set
delay time.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level)
OVER SPEED 9.12.
- Used as over speed contact.
- When contact is input, operation mode of Gen-set will switch according to set warning level after set
delay time.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level)
OCGR 9.13.
- Used as OCGR contact.
- When contact is input, operation mode of Gen-set will switch according to set warning level after set
delay time.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level)
BREAKER AUX
9.14.
- Used as breaker auxiliary contact.
- Setup : TYPE(N/O, N/C),
Menus that are influenced
Setup
Description
[SYSTEM] → [BREAKER AUX]
[USE]
Use of breaker aux
UVR SIGNAL 9.15.
- Used as start contact in [AUTO] mode.