REV. N
NeoGCP i7 PLUS+
- 23 -
- If [FIRE-RUN] is not input or [EM’CY STOP] is input or Shutdown Alarm occurs, Gen-set will stop and
status will switch to the mode setup before [FIRE].
Menus that are influenced
Setup
Description
[DI-CONFIG] → [EM’CY STOP]
User setup
[EM’CY STOP] input
SCHEDULED-RUN 6.14.
- Will not activate if [SCHEDULED-RUN START] time is set after [SCHEDULED-RUN STOP] time, or if
[SCHEDULED-RUN START] time is set same as [SCHEDULED-RUN STOP] time.
- Scheduled run only activates in [AUTO] mode.
- If Mains Off is input during scheduled-run, status will automatically switch to [AUTO] mode.
Menus that are influenced
Setup
Description
[CONTROL] → [SCHEDULED-RUN]
User setup
User setup related to scheduled-run