REV. N
NeoGCP i7 PLUS+
- 40 -
10. DO-CONFIG
- Digital Output(DO) Setup.
- Setup possible in Stop mode. (Some items excluded)
DO List
Description
DO List
Description
C_PRE-CRANK
Pre-heat
F_OVER VOLTAGE
Over voltage
C_CRANK
Start motor
F_UNDER VOLTAGE
Under voltage
C_GOVERNOR
Solenoid
F_OVER CURRENT
Over current
C_BREAKER CLOSE
Breaker close
F_OCGR
Ground over current
C_BREAKER OPEN
Breaker open
F_OVER FREQ
Over frequency
C_ALARM BUZZER
Alarm
F_UNDER FREQ
Under frequency
C_ALARM RESET
Alarm Release
F_OVER SPEED
Over speed
C_IDLE SPEED
IDLE Speed
F_UNDER SPEED
Under speed
C_RATED SPEED
Rated Speed
F_FAIL TO START
Start failure
C_AIRHEATER
Air Heater
F_FAIL TO STOP
Stop failure
C_USER TIMER
User Timer
F_FAIL TO BUILD-UP
Build-up failure
F_COOLANT TEMP HIGH
Coolant high temp
S_MAINS ON
Mains on status
F_COOLANT TEMP LOW
Coolant low temp
S_MAINS OFF
Mains off status
F_OIL PRESS HIGH
Oil high press
S_GEN START
Gen-set start
F_OIL PRESS LOW
Oil low press
S_GEN RUNNING
[RUN] status
F_OIL TEMP HIGH
Oil high temp
S_BLOCK MODE
[BLOCK] mode
F_OIL TEMP LOW
Oil low temp
S_MANUAL MODE
[MANUAL] mode
F_USER TEMP HIGH
User temp high
S_AUTO MODE
[AUTO] mode
F_USER TEMP LOW
User temp low
S_FIRE-RUN MODE
[FIRE] mode
F_FUEL LEVEL HIGH
Fuel level high
S_ALL ALARM
All Alarm
F_FUEL LEVEL LOW
Fuel level low
S_WARNING
Warning
F_BAT VOLT HIGH
Battery voltage high
S_HEAVY FAULT
SHT, TRIP+STOP
TRIP+SHT
F_BAT VOLT LOW
Battery voltage low
S_TRIP FAULT
TRIP
F_USER PRESS HIGH
User press high
S_STOP FAULT
STOP
F_USER PRESS LOW
User press low
S_SHUTDOWN FAULT
SHT
F_COOLANT LEVEL LOW
Coolant level low
S_FUEL LEVEL
FUEL LEVEL
F_USER FAULT 1~10
User fault contact