15. PROTECTION TEST
- Test setup can be changed in [PROTECTION].
Items
Description
Setup
OVER VOLTAGE TEST
200% of rated voltage at start-up
Change in [PROTECTION]
UNDER VOLTAGE TEST
-
OVER CURRENT TEST
200% of rated current at start-up
OCGR TEST
200% of OCGR at start-up
OVER SPEED TEST
-
OIL PRESS S/W TEST
Suggested to check actual wiring
COOLANT S/W TEST
Suggested to check actual wiring
COOLANT TEMP HIGH
TEST
-
OIL PRESS LOW TEST
-
16. HISTORY
- Alarm History check is possible only in [BLOCK] mode.
- Check up to 30 Gen-set operation information in sequence in case of alarm history, cranking output
history and alarm occurrence.
- Start motor ON/OFF record stored in ALARM HISTORY.
17. Fault Items
Generator Related Fault Items 17.1.
Items
Alarm Level
Delay
Time
Sequence
applied
Not use
Warning
Trip
Stop
Shutdown
OVR
Setup
Always
Gen Voltage detected higher than set value
UVR
Setup
Running
Gen Voltage detected lower than set value
OCR
Setup
Always
Gen Current detected higher than set value
OCGR
Setup
Always
Gen Ground Current detected higher than set value
OCGR input
OFR
Setup
Always
Gen Frequency detected higher than set value
UFR
Setup
Running
Gen Frequency detected lower than set value
FAIL TO BUILD-
UP
0[s]
Build-Up
If voltage, frequency, and RPM don’t build-up within set time after cranking.
Nominal Range : Under Voltage < Gen Voltage < Over Voltage
Under Frequency < Gen Frequency < Over Frequency
Under speed < Engine Speed(RPM) < Over speed