NeoGCP i7 PLUS+
- 38 -
ALARM RESET 9.24.
- Used as Alarm reset contact.
- When Alarm occurs and is released, Alarm status will be initialized when signal is input.
- When Alarm occurs and is not released, only Alarm Horn will be initialized when signal is input.
- Setup : TYPE(N/O, N/C),
IDLE RUN 9.25.
- Used as IDLE contact.
- Operation status will switch to [IDLE] when contact is input.
- Setup : TYPE(N/O, N/C)
GEN VOLTAGE CHANGE 9.26.
- Used as generator voltage change contact.
- It changes to the voltage state, when contact is input after changing the generator wiring.
(ex) 380V -> 220V / 440V -> 380V
- Setup : TYPE(N/O, N/C)
BUZZER STOP 9.27.
- Used as buzzer stop contact.
- The buzzer sound stops immediately, when the contact is input.
- Setup : TYPE(N/O, N/C)
USER TIMER INPUT 9.28.
- Used as user timer start contact.
-The set user timer is activated, when the contact is input. After the operation is completed, it is output to
the set relay.
- After the set time, it is turned ON/OFF as a user timer relay.
(User timer ON/OFF delay setting: 0.0~999.0 sec)
- Setup : TYPE(N/O, N/C)