Programming manual
Programming events 61
SCENARIO
DEFINITIONS
There are 50 scenarios available in the list. Selecting one of them will allow you to use the
programming area, alongside the list, to configure each of the 10 outputs available.
For each of these it is necessary to indicate the output (from those configured) and the
activation type:
•
0/100
- percentage value for dimmer outputs or analogue outputs of a Flex5 expansion.
•
ON
- command that activates the output or, if it is a “switching” type output, changes its
operating status.
•
OFF
- command that deactivates the output
•
Force ON
- command that activates the output
•
Toggle
- command that changes the activation status of the output
SCENARIOS ON
EVENTS
To assign one of the programmed scenarios to the each event, go to the programming section
of the event.
The “Output scenarios” section provides two programming fields for the selection of the
scenarios, one relating to activation of the event and the other to its restoral.
12-4
Periodic events
The Prime control panel provides 4 periodic events.
Programming of these events includes the date and time of the first activation and the
periodicity.
The activation of the first periodic event can be driven by other events (see the "Activate
periodic event" option in
Table 12-6: Single event parameters
).
Note
Set the date and time of first occurrence following the current date and time of the control panel.
12-5
Programmable events
A group of events is available for installer programming. Event activation and restoral depend on a
combination of other control panel events based on logical operations, counters and timers.
On account of their enhanced flexibility, special attention is required during the programming
and testing phases of the programmable events. The effects of the programmable events
must always be rigorously tested.
Each programmable event consists of a mathematical-logic formula of events, timers and
counters. The programming structure consists of:
• 30 events programmable for Prime060S and Prime060L, 50 for Prime120L and 60 for
Prime240L
• 40 timers
• 10 counters
Via software
Click-on the
Events
button on the menu on the left then from the “Programming - Events list”
section on the right, select the “Programmable event” option in the “Event type” field.
Table 12-7: Periodic event parameters
Parameter Software section Installer menu section
Periodic event
Programming field for the date and time of the first
“Periodic Event”
You can write the setting on the control panel by
means of the Write on control panel button.
Control panel
parameters,
Periodic event
Other parameters, Pe-
riodic Ev., Periodic
Event "x",
Time per. Event
Periodic event Inter-
val
This parameter allows you to set the interval
between “Periodic events” (expressed in minutes or
hours).
To disable the “Periodic event” completely, set “0”.
PeriodicInterval
Options, PeriodicEv.
InMin
Continuous periodic
event
If enabled, the system will generate the
corresponding periodic event regardless of its initial
date/time. The event will be generated when the
programming session is exited, or when the system
starts up, and will be generated continuously when
the set period expires.
Options, Per.Ev. Con-
tinuous
Write on control panel
This button writes the setting on the control panel. Not available