EasyManua.ls Logo

INIM Electronics Prime - 13-4 Programming KNX interface

INIM Electronics Prime
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming manual
Programming the PrimeLAN board 67
13-4
Programming KNX interface
By clicking on the
PrimeLAN settings
button on the menu on the left, you will access the
“Programming KNX” section.
This section contains three further sections, one for setting the parameters of the KNX
gateway and communicating with it, the other boards for translating of signals to and from the
KNX system.
CONTROL PANEL
CODE
When necessary for the security system, it is a good idea for the installer to create an
additional Prime user equipped with a PIN code, capable of carrying out commands and
actions from KNX devices even when validation from the Prime control panel is required.
FROM CONTROL
PANEL TO KNX
This section allows you to define which panel events must be communicated to the KNX
system via commands or actions and to translate these into "KNX telegrams".
These events (maximum of 3000) are added to the list below via the appropriate button .
KNX SOLUTIONS
The "Add KNX telegram" window, which is opened by the button
...
, provides the
Open
button
to open “.esf” format files, the solution files of KNX programming software.
Once one of these solutions has been selected the window will show a tree structure with the
various elements of the KNX system and the relative telegrams. A double click on one of these
items allows you to import the telegram into the appropriate box.
FROM KNX TO
CONTROL PANEL
This section allows you to define which signals from the KNX system in the form of "KNX
telegrams" must be communicated to the Prime control panel and which actions must be
performed.
These events are added to the list below via the appropriate button for a maximum of
3000 actions.
Table 13-4: KNX gateway parameters
Parameter Software section
Enable KNX function
This option enables communication between Prime and KNX systems.
Programming
KNX, General
settings
IP address /
UDP Port /
Group address
of the KNX gateway
Check boxes for setting the KNX-IP interface gateway data.
Control panel code
Check box to indicate the Prime user code for commands and actions from KNX
devices.
Polling time
Time interval in seconds of interrogation of the Prime control panel.
KeepAlive time
Time interval in seconds between two successive supervision signals of the KNX
gateway.
Table 13-5: Signals from Prime control panel to KNX system
Parameter Software section
Value
Check box to indicate the event type.
Programming
KNX, From control
panel to KNX
Element
Check box to indicate the parameter of the type of event that defines the event
itself.
Element category
Check box to indicate the category of the element that defines the event itself.
KNX telegram
Check boxes to enter the KNX telegram to be sent following the corresponding
event.
...
Button to open the "Add KNX telegram" window.
Delete
Button to delete the corresponding event from the list