Programming manual
Compliance with rules in force 79
ZONES
Zones configured as “24H”, “Automation” are non-compliant.
Zones programmed as “Arm”, “Disarm”, “Switch” or “Follow” comply only when activated by
keyswitches with more than 10,000 code combinations.
An input is set up for system fault management.
For zones with the “Fault zone” option enabled, it is necessary to eliminate from the relative
alarm event the programming of an external sounder/flasher in the “Outputs” parameter. You
can programme indoor sounderflashers via the “Other outputs” option.
SOUNDER/
FLASHERS
The system must include a self-powered outdoor sounder/flasher for intrusion-alarm event
signalling.
TELEPHONE
DIALER/
COMMUNICATOR
The telephone dialer must be enabled.
If you use a digital dialer or voice dialer with SmartLogos30M board for transmissions, a
telephone number must be reserved for the following events:
• All events generated by zones with the “Hold-up” attribute.
• All events generated by “Instant”, “Delayed”, “Delayed unhidden” and “Route”
• All events generated by terminal, peripheral and control panel tamper.
• All faults detected by the control panel.
PARAMETERS
The “Alarm Cycles” parameter of each zone must be set between 3 and 10.
The “Mains fail.Delay” parameter must be set at no more than 1 minute.
The “Entry Time” of each partition must be set at a maximum of 45 seconds.
You must enable the “Priority” option for any alarm events associated with “Hold-up” zones.
“Failed to arm” and “Forced arming” events must be saved to the Events log.
Reader LED OFF
Table 4-6: Parameters for
compliance
Regulatory
compatibility,
Parameters
50131
50131ReaderLedOFF
Enabled
Hide status
50131StatHidden
Enabled
Hide icons
50131IconsHidden
Enabled
Alarm delay
50131AlarDelayed
Enabled
Fault memory LED
50131WarnLedMem
Enabled
Reader Buzzers OFF
Table 3-4: Parameters
common to all readers
Reader parameters
ReaderBuzzer OFF
Disabled
Bypass tamper in the event
of bypassed zones
Table 4-3: Control panel
options
Control panel
parameters
BypassAlsoTamper
Disabled
Zone fuse fault
Table 4-6: Parameters for
compliance
Regulatory
compatibility
Forced arming
faults
Other parameters,
FaultForNotReady
Zone fuse fault
Enabled
I-BUS fuse fault
IBUS fuse fault
Enabled
Low battery
Low battery
Enabled
Mains failure
Mains failure
Enabled
Telephone line down
Tel. line down
Enabled
Jamming
Jamming
Enabled
Low battery wireless
Low battery WLS
Enabled
Wireless zone loss
WLS zone loss
Enabled
Loss or tamper ongoing
LossTamp.ongoing
Enabled
Requires code
Table 3-2: Parameters for
single keypads
Configured keypads ,
selected keypad,
General, Advanced
Shortcut Func.keys,
"Fx", Options, Re-
quires code
Enabled
Clear call queue on disarm
Table 5-1: Parameters for
single partitions
Partitions,
selected partition
Partitions, "parti-
tion", StopTelOn Dis-
arm
Disabled
Table 19-1: EN50131 grade 2 - Enablement of options