42 Installation
Anti-intrusion control panels
3-5-1
N.C./N.O. Balancing
For N.C. (normally closed) and N.O. balancing (normally open), it is
possible to detect two distinct zone conditions:
standby
•alarm
For each of these, the control panel reads different resistance values on
the terminal, expressed below in Ohm.
If you wish the detector to signal tamper events, connect the detector
“Tamper” terminal to a “24h” zone on the control panel.
3-5-2
Single balancing
Single zones can discriminate 3 conditions on the entire terminal:
standby
•alarm
tamper (short-circuit)
For each of these, the control panel reads different resistance values on
the terminal, expressed below in Ohm.
If you wish the detector to signal tamper events, connect the detector
“Tamper” terminal to a “24h” zone on the control panel.
3-5-3
Double balancing
Double balancing discriminates 4 distinct conditions on the zone terminal:
standby
•alarm
tamper (short-circuit)
tamper (wire cutting)
For each of these, the control panel reads different resistance values on
the terminal, expressed below in Ohm.
Ohm Zone N.O.
> 2 x 3900 + 6800 alarm standby
> 2 x 3900 + 6800 alarm standby
3900 + 6800 alarm alarm
2 x 3900 alarm alarm
3900 standby alarm
0 standby alarm
Alarm
+12V GND
Tamper
Ohm Zone
> 6800 alarm
6800 standby
0tamper
Alarm
+12V GND
Tamper
6K8Ohm
1/4W
Ohm Zone
> 6800 tamper (wire cutting)
6800 alarm
6800 / 2 standby
0 tamper (short-circuit)
Alarm
+12V GND
Tamper
6K8Ohm
1/4W