104 Compliance with rules in force
Anti-intrusion control panels
Chapter 8
COMPLIANCE WITH
RULES IN FORCE
In order to guarantee compliance with the regulations in force, you must adhere to the
following guidelines:
nBy/X readers must be equipped with devices that protect them against forced-
opening of their casings (EN50131 grade 2) and dislodgement from their placements
(CEI 79-2 level II and EN50131 grade 3) , in compliance with Level 3, as indicated in
paragraph 3-2-9 Installing nBy/X readers.
The dislodgement protection of the control panel mod. Tamper NO must be mounted
(CEI 79-2 level II and EN50131 grade 3).
JOY, Aria/HG, nCode and Concept keypads must be equipped with enabled tamper-
protection devices, as indicated in paragraph 3-3-2 Addressing the keypads.
FLEX5/U and IB100-RU devices must be mounted inside the enclosure of
SmartLiving 1050L, 10100L, 1050L/G3 and 10100L/G3 control panels, or must be
equipped with a device that protects them against forced-opening of their casings
(EN50131 grade 2) and dislodgement from their placements (CEI 79-2 level II and
EN50131 grade 3).
IB100-RP and IB100-A devices cannot be used in configurations with security grade
3, unless equipped with a device that protects against dislodgement.
The lines relating to the intrusion-detection zones must be configured as 'Double
balancing' with double EOL resistors, or as Single balancing with single EOL resistor.
They must also be equipped with devices which protect them against the forced-
opening of their casings.
Terminal tamper, peripheral tamper and control-panel tamper events must trigger
audible signals (sounder signals) for a period of not less than 3 minutes.
The output activated by the previously mentioned tamper events must be different
from the output activated by alarms signals.
All Code PINs must have 6 digits.
If a Timer is used for automatic-arming operations, the Pre-arm times must be
programmed separately for each partition (the Pre-arm time must not be set at 0).
CEI 79-2 LEVEL II
Specifically, to guarantee CEI 79-2 compliance of devices, the following options must be
programmed as follows.
The following options must not be activated in the “Panel Options” section:
•• ReaderBuzzer OFF
•• BypassAlsoTamper
•• OpenZonesArmLock
•• 50131ReaderLedOFF
•• 50131StatHidden
•• 50131IconsHidden
•• 50131AlarDelayed
•• 50131WarnLedMem
Do not enable any of the “FaultsNotReady” options from the “Other parameters”
section.
The “Requires code” option - from the “Keypads - Choose peripheral - Options”
section - must be enabled for every keypad and shortcut in use.
The “Entry Time” parameter of each partition must be no more than 60 seconds.
EN50131, GRADE 2
Compliancy with EN50131 Grade 2 is guaranteed by observing the following guidelines.
In the “Panel options” section, enable:
•• Keypad lockout
•• OpenZonesArmLock
•• NoUserTamp.reset
•• 50131ReaderLedOFF
•• 50131StatHidden
•• 50131IconsHidden