Installation and programming manual
Compliance with rules in force 105
•• 50131AlarDelayed
•• 50131WarnLedMem
The following options must not be activated in the “Panel Options” section:
•• ReaderBuzzer OFF
•• BypassAlsoTamper
In the section “Other parameters - FaultForNotReady”, enable the following options:
•• Zone fuse fault
•• IBUS fuse fault
•• Low battery
•• Mains failure
•• Tel. line down
•• Jamming
•• Low battery WLS
•• WLS zone loss
•• LossTamp.ongoing
Zones configured as “24H”, “Automation” are non-compliant.
Zones programmed as “Arm”, “Disarm”, “Switch” or “Follow” comply only when
activated by keyswitches with more than 10,000 code combinations.
An input is set up for system fault management.
You must delete any programming relating to outdoor sounderflashers - from the
respective alarm event in the “Outputs” section - for all zones with the “Fault Zone”
attribute. You can programme indoor sounderflashers via the “Other outputs” option.
The telephone dialer must be enabled.
The system must include a self-powered outdoor sounderflasher for intrusion-alarm
event signalling.
If you use a digital dialer or voice dialer with SmartLogos30M board for
transmissions, a telephone number must be reserved for the following events:
•• All events generated by zones with the “Hold-up” attribute.
•• All events generated by “Instant”, “Delayed”, “Delayed unhidden” and “Route”
•• All events generated by terminal, peripheral and control panel tamper.
•• All faults detected by the control panel.
The “Alarm Cycles” parameter of each zone must be set between 3 and 10.
The “Mains fail.Delay” parameter must be set at no more than 1 minute.
The “Requires code” option on the function-key shortcuts must be enabled for all the
assigned shortcuts.
The “StopTelOn Disarm” partition option must not be enabled.
The “Entry Time” of each partition must be set at a maximum of 45 seconds.
You must enable the “Priority” option for any alarm events associated with “Hold-up”
zones.
“Failed to arm” and “Forced arming” events must be saved to the Events log.
The programmed “LowBattery delay” must not be programmed at more than 5
minutes.
EN50131-3, GRADE 3
Compliance with EN50131-3 grade 3 is guaranteed by adding to the above-mentioned
requirements the following:
In the “Parameters” section, enable option “50131 Grade 3”.
If the installation uses detectors with an anti-mask function, each anti-mask signal
must be managed as follows:
•• Prepare an input terminal for the anti-mask signal connection.
•• Programme the following parameters:
- “Description”: assign an explanatory description to the signal
- “Fault zone”: enable this option
- “NoArmIfNotReady”: enable this option
Use an ATS4 notification appliance:
•• protocol: SIA-IP with encryption
•• interface: SmartLAN/G or SmartLAN/SI
EN50131-6, GRADE 3
Compliance with EN50131-6 grade 3 is guaranteed for SmartLiving control panel
models 1050/G3, 1050L/G3 and 10100L/G3 without additional requirements.
Compliance with EN50131-6 grade 3 is guaranteed for SmartLiving control panel
models 505/G3, 515, 1050, 1050L and 10100L without additional requirements.
Remove the power supply/transformer module (Table 2-6: Control panels -
description of parts, D).
Install an EN50131-6 Grade 3 certified power supply unit alongside the control panel
enclosure. This power supply will output the power for the control panel and the
following signals: