Installation and programming manual
Compliance with rules in force 105
•• 50131AlarDelayed
•• 50131WarnLedMem
• The following options must not be activated in the “Panel Options” section:
•• ReaderBuzzer OFF
•• BypassAlsoTamper
• In the section “Other parameters - FaultForNotReady”, enable the following options:
•• Zone fuse fault
•• IBUS fuse fault
•• Low battery
•• Mains failure
•• Tel. line down
•• Jamming
•• Low battery WLS
•• WLS zone loss
•• LossTamp.ongoing
• Zones configured as “24H”, “Automation” are non-compliant.
• Zones programmed as “Arm”, “Disarm”, “Switch” or “Follow” comply only when
activated by keyswitches with more than 10,000 code combinations.
• An input is set up for system fault management.
• You must delete any programming relating to outdoor sounderflashers - from the
respective alarm event in the “Outputs” section - for all zones with the “Fault Zone”
attribute. You can programme indoor sounderflashers via the “Other outputs” option.
• The telephone dialer must be enabled.
• The system must include a self-powered outdoor sounderflasher for intrusion-alarm
event signalling.
• If you use a digital dialer or voice dialer with SmartLogos30M board for
transmissions, a telephone number must be reserved for the following events:
•• All events generated by zones with the “Hold-up” attribute.
•• All events generated by “Instant”, “Delayed”, “Delayed unhidden” and “Route”
•• All events generated by terminal, peripheral and control panel tamper.
•• All faults detected by the control panel.
• The “Alarm Cycles” parameter of each zone must be set between 3 and 10.
• The “Mains fail.Delay” parameter must be set at no more than 1 minute.
• The “Requires code” option on the function-key shortcuts must be enabled for all the
assigned shortcuts.
• The “StopTelOn Disarm” partition option must not be enabled.
• The “Entry Time” of each partition must be set at a maximum of 45 seconds.
• You must enable the “Priority” option for any alarm events associated with “Hold-up”
zones.
• “Failed to arm” and “Forced arming” events must be saved to the Events log.
• The programmed “LowBattery delay” must not be programmed at more than 5
minutes.
EN50131-3, GRADE 3
Compliance with EN50131-3 grade 3 is guaranteed by adding to the above-mentioned
requirements the following:
• In the “Parameters” section, enable option “50131 Grade 3”.
• If the installation uses detectors with an anti-mask function, each anti-mask signal
must be managed as follows:
•• Prepare an input terminal for the anti-mask signal connection.
•• Programme the following parameters:
- “Description”: assign an explanatory description to the signal
- “Fault zone”: enable this option
- “NoArmIfNotReady”: enable this option
• Use an ATS4 notification appliance:
•• protocol: SIA-IP with encryption
•• interface: SmartLAN/G or SmartLAN/SI
EN50131-6, GRADE 3
Compliance with EN50131-6 grade 3 is guaranteed for SmartLiving control panel
models 1050/G3, 1050L/G3 and 10100L/G3 without additional requirements.
Compliance with EN50131-6 grade 3 is guaranteed for SmartLiving control panel
models 505/G3, 515, 1050, 1050L and 10100L without additional requirements.
• Remove the power supply/transformer module (Table 2-6: Control panels -
description of parts, D).
• Install an EN50131-6 Grade 3 certified power supply unit alongside the control panel
enclosure. This power supply will output the power for the control panel and the
following signals: