Installation and programming manual
Options and programming methods 95
Within 70 seconds the control panel will reset to default settings, re-enroll all the
peripherals currently on the I-BUS and, if a keypad is connected, will ask you to select
the Language.
Reset to factory default will not clear the events log.
Via Keypad
1. Access the “Default settings” section:
Type in Code
(Installer)
, PROGRAMMING Default settings .
2. Use keys and to select the function thenpress :
Factory data
If you select this option, the control panel will reset entirely to default settings.
ATTENTION!
This operations deletes all the previously programmed parameters.
Learn zone bal.
If you select this option, the control panel will learn (save to memory) automatically all
the balancing settings of all the zones (Patent Pending).
The zone-balancing options are:
Normally Open
Normally Closed
Balancing (Single balancing)
Double balancing
Rollerblind with EOL
The balancing settings which are not acquired accurately are:
Rollerblind without EOL (which is classified as a normally-closed generic zone)
Double zone without EOL (which is classified as a normally-closed generic zone)
Double zone with EOL (which is classified as a generic zone with Double balancing)
In order to allow accurate acquisition of the balancing settings of all the zones, you
must:
•• Wire and select the balancing settings of all the zones.
•• Ensure that all the zones are in standby status
•• Select the “Learn zone bal.” option.
•• Verify that the operation has been carried properly and that all the settings are
accurate (if any zones are not in standby status during this process their settings
will not be acquired accurately).
•• Set manually any inaccurate settings.
Autoenroll periph.
If you select this option, the control panel will enroll automatically all the peripherals it
finds on the I-BUS.
CONTACTIDDefault
If you select this option, the control panel will reset to default settings all the event
codes used for the CONTACT-ID protocol (refer to Appendix A, Technical terminology
and Glossary).
CONT-ID enumer.
If you select this option, the control panel (after confirmation) will implement
incremental numbering (from “1”) in the “CCC” field of the CONTACT-ID protocol (refer
to Appendix A, Technical terminology and Glossary) for the event relating to the zone.
SIA defaults
If you select this option, the control panel (after confirmation) will reset all the factory
default settings on SIA parameters of all events.
DeletePrg.events
Press the key to delete all the events saved to the control panel events log
(activation and restoral events):
All outputs
All calls
All options
WLS data reset
Press the key to delete all the data relating to the Air2-BS200 device.
Note
The data relating to the wireless detectors and keyfobs will not reset on the control panel, nor will
the devices simulated by the Air2-BS200 transceiver be deleted from the configuration.
3. The control panel will ask for confirmation of this command (press ).
CONTINUE?OK=YES
PROGRAMMING
Language
Messages
Default settings
Default settings
Factory data
Learn zone bal.
AutoenrolPeriph.