5. Quick Setup
- 71 -
5
CONTINUE Para. Parameter name Default Commission
Select control mode F0-01 Motor 1 control mode 0
0: SVC control
1: FVC control
2: V/F control
Select frequency reference
setting channel
F0-03 Main frequency reference setting
channel selection
0
If F0-08 is frequency reference
0: Digital setting F0-08 (pressing
or can revise
F0-08 easily, and the revised value won’t be cleared even
after power off)
1: Digital setting F0-08 (pressing
or can change
F0-08 easily, but the revised value would be cleared after
power off)
2: AI1
3: AI2
4: AI3
5: Pulse setting (DI5)
6: Multi-reference setting
7: Simple PLC
8: PID
9: Communication setting
Set F0-08 F0-08 Preset frequency 50.00
If AI1 is frequency reference
0 Hz to F0-10
Set AI1 F4-13 AI curve 1 minimum input 0.00
If AI2 is frequency reference
0 V to F4-15;
F4-14 Corresponding percentage of AI1
minimum input
0.0
-100.0% to 100.0%
F4-15 AI1 maximum input 10.00
F4-13 to 10.00 V
F4-16 Corresponding percentage of AI1
maximum input
100.0
-100.0% to 100.0%
Set AI2 F4-18 AI curve 2 minimum input 0.00
0 V to F4-20;
F4-19 Corresponding percentage of AI2
minimum input
0.0
-100.0% to 100.0%
F4-20 AI2 maximum input 10.00
F4-18 to 10.00 V
F4-21 Corresponding percentage of AI2
maximum input
100.0
-100.0% to 100.0%