Wiring
‑64‑
Note
● [1] The range of the internal +24 V power supply is 20 V to 28 V, with maximum
operating current being 200 mA.
● [2] DI8 and DI9 are high‑speed DIs that must be used according to their functions
assigned.
● [3] Use the shielded twisted pairs for pulse terminals, with both ends of the shield
connected to PE. Connect GND and signal GND of the host controller properly.
● [4] The DO power supply (voltage range: 5 V to 24 V) needs to be prepared by
users. The DO terminals support a maximum voltage of 30 VDC and a maximum
current of 50 mA.
● [5] Use the shielded twisted pair cable as the encoder frequency‑division cable,
with both ends of the shield connected to PE. Connect GND and signal GND of the
host controller properly.