IPE300 series engineering VFD Function parameter list
-112-
Function
code
Name
Description
Default
Modify
limit of the running frequency is used for
running.
Setting range: P00.05P00.03 (Max. output
frequency)
P00.05
Lower limit of
running frequency
The lower limit of the running frequency is the
lower limit of the output frequency of the VFD,
When the set frequency is lower than the lower
limit of the running frequency, the lower limit of
the running frequency is used for running.
Note: Max. output frequency Upper limit of
frequency ≥ Lower limit of frequency
Setting range: 0.00HzP00.04 (Upper limit of
running frequency)
0.00Hz
P00.06
Setting channel of
A frequency
command
0: Keypad
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDIA
5: Simple PLC program
6: Multi-step speed running
7: PID control
8: Modbus communication
9: PROFIBUS/CANopen/DeviceNET
communication
10: Ethernet communication
11: High-speed pulse HDIB
12: Pulse train AB
13: EtherCat/Profinet communication
14: PLC
15: Reserved
0
P00.07
Setting channel of
B frequency
command
15
P00.08
Reference object
of B frequency
command
0: Max. output frequency
1: A frequency command
0
P00.09
Combination mode
of setting source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max(A, B)
5: Min(A, B)
0