IPE300 series engineering VFD Function parameter list
-118-
output frequency)
P01.10 setting range: 0.00–30.00s
P01.11 setting range: 0.0–100.0%
P01.12 setting range: 0.0–50.0s
FWD/REV running
deadzone time
This function code indicates the transition time
specified in P01.14 during FWD/REV rotation
switching. See the following figure:
Output frequency f
Forward
Reverse
Deadzone
time
Time t
Starting
frequency
Switch over after
zero frequency
Switch over after
starting frequency
Setting range: 0.0–3600.0s
FWD/REV running
switching mode
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop speed
with a delay
Stop speed
detection mode
0: Detect by the set speed (unique in space
voltage vector control mode)
1: Detect by the feedback speed
Stop speed
detection time
Terminal-based
running command
protection at
power-on
When the channel of running commands is
terminal control, the system detects the state of
the running terminal during power-on.
0: The terminal running command is invalid at
power-on. Even the running command is
considered as valid during power-on, the VFD
does not run and it keeps the protection state
until the running command is canceled and
enabled again.
1: The terminal running command is valid at
power-on. If the running command is considered
as valid during power-on, the VFD is started
automatically after the initialization.