IPE300 series engineering VFD Function parameter list
-120-
Functio
n code
Name
Description
Default
Modify
power-off
re-powered on.
Output frequency
Running
Power off
Power on
Running
t
t1 t2
t1=P01.22
t2=P01.23
Setting range: 0.03600.0s (Valid only when
P01.21=1)
P01.23
Start delay
After a VFD running command is given, the VFD
is in standby state and restarts with the delay
defined by P01.23 to implement brake release.
Setting range: 0.0600.0s
0.0s
P01.24
Stop speed delay
0.0600.0s
0.0s
P01.25
Open-loop 0Hz
output selection
0: Output without voltage
1: Output with voltage
2: Output with the DC braking current for stop
0
P01.26
DEC time for
emergency stop
0.060.0s
2.0s
P01.27
Time of starting
segment of DEC S
curve
0.050.0s
0.1s
P01.28
Time of ending
segment of DEC S
curve
0.050.0s
0.1s
P01.29
Short-circuit
braking current
When the VFD starts in direct start mode
(P01.00=0), set P01.30 to a non-zero value to
enter short-circuit braking.
During stop, if the running frequency of VFD is
lower than the starting frequency of brake for
stop (P01.09), set P01.31 to a non-zero value to
enter short-circuit braking for stop, and then carry
out DC braking in the time set by P01.12. (See
descriptions for P01.09P01.12.)
P01.29 setting range: 0.0150.0% (VFD)
P01.30 setting range: 0.050.0s
P01.31 setting range: 0.050.0s
0.0%
P01.30
Hold time of
short-circuit
braking for start
0.00s
P01.31
Hold time of
short-circuit
braking for stop
0.00s
P01.32
P01.34
Reserved