Note: After a virtual terminal is enabled, the state
of the terminal can be changed only in
communication mode. The communication
address is 0x200A.
Used to define the relationship between the
analog input voltage and its corresponding
setting. When the analog input voltage exceeds
the range from the upper limit to the lower limit,
the upper limit or lower limit is used.
When the analog input is current input,
0mA–20mA current corresponds to 0V–10V
voltage.
In different applications, 100.0% of the analog
setting corresponds to different nominal values.
See the descriptions of each application section
for details.
The following figure illustrates the cases of
several settings: