1: Valid during running, cleared after stop
2: Valid during running, cleared after a stop
command is received
0x000–0x111
Ones place: Action selection at power-off
during frequency adjusting through digitals.
0: Save the setting at power-off.
1: Clear the setting at power-off.
Action selection at power-off during
frequency adjusting through Modbus
communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
Hundreds place: Action selection at
power-off during frequency adjusting through
other communication methods
0: Save the setting at power-off.
1: Clear the setting at power-off.
Used to set the initial electricity consumption.
Initial electricity consumption = P08.48*1000
+ P08.49
P08.48 setting range: 0–59999 kWh (k)
P08.49 setting range: 0.0–999.9 kWh
Used to enable magnetic flux braking.
0: Disable
100–150: A larger coefficient indicates
stronger braking.
The VFD can quickly slow down the motor by