Setting Alarm Thresholds
· Alarm thresholds can be set on the Detail Data
page under the Data Menu.
· Voltage thresholds are set using the Update Set-
tings button under the Voltage Alarm.
· Selecting the Voltage Alarm
Update Settings button will
reveal a menu for the high
(upper) voltage threshold as
well as low voltage thres-
hold. The time delay for the
respective thresholds will
determine the duration the
state must be true to activate
the alarm.
· Selecting the Current Alarm
Update Settings button will
reveal a menu for the high (up-
per) current threshold as well
as low current threshold. The
time delay for the respective
thresholds will determine the
duration the state must be true
to activate the alarm. Current
thresholds are based on a per-
centage of the breaker rating
which is set under the Configu-
ration > Breaker Size page.
INFORMATION
Setting any threshold to “0” will disable the alarm.
It is suggested that the low current threshold be
disabled unless there is a specific requirement.

Table of Contents

Other manuals for janitza UMG 804

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the janitza UMG 804 and is the answer not in the manual?

janitza UMG 804 Specifications

General IconGeneral
Brandjanitza
ModelUMG 804
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals