6 Safety Manual
33
6.2 Validity of the safety manual
6.3 Special operating statuses
6.3.1 Behavior after a power failure
Analog output issues 3.6 mA; relay output (extra code) limit value is deactivated.
After the return of the mains voltage, the device starts as described in Chapter 5 and converts the measured value at the ana-
log input in the configured output signal.
6.3.2 During setup data transfer
If LED illuminates yellow, the device is transferred to a safe
state until the setup data reaches the device and a data com-
parison is carried out.
6.3.3 After alteration of the configuration level (at the device or through setup)
The device carries out a plausibility check that can also trigger an error message.
v Chapter 12 "What to do, if ..." "Check dependent parameters"
v Chapter 11 "Error messages"
Note
The evaluation described in this safety manual in terms of functional safety and display of certificates is valid for
the specified transmitter in SIL operation, including probe versions.