7 Configuration
74
7.7 RS485 interface
7.6.2 Limit value
Here, the fixed switching point (1) is set. Measuring range start to 0
to measuring range end in
°C/°F/text
7.6.3 Switch difference
The switching differential determines the gap between
the switch-on and switch-off threshold (2).
0 to 1 to 100 °C/°F/text
7.6.4 Switching behavior
standard,
left,
right
7.6.5 Switch on delay
The relay only switches on or off after the entered time
has elapsed.
0 to 9999 s
7.6.6 Switch off delay
0 to 9999 s
Parameter Comment
Value range
(default setting in bold)
7.7.1 Baud rate
Protocol: Modbus slave 9600, 19200, 38400, 57600,
115200
Parameter Comment
Value range
(default setting in bold)