7 Configuration
65
7.4.2 Linearization
Comment Measuring range
Linear No sensor linearization -
Pt100 IEC 60751:2008 -200 to +850 °C
Pt500, Pt1000 IEC 60751:2008 -200 to +850 °C
Pt50 GOST, Pt100 GOST GOST 6651- 2009 A.2 -200 to +850 °C
Ni 100, Ni 500, Ni1000 DIN 43760:1987-09 -60 to +250 °C
Ni 100 GOST GOST 6651-2009 A.5 -60 to +180 °C
Cu 50 GOST, Cu 100 GOST GOST 6651-2009 A.3 -180 to +200 °C
Pt13Rh-Pt "R" DIN EN 60584-1:2014 -50 to +1768 °C
Pt10Rh-Pt "S"
Pt30Rh-Pt6Rh "B" -50 to +1820 °C
Fe-CuNi "J" -210 to +1200 °C
Cu-CuNi "T" -200 to +400 °C
NiCr-Ni "E" -200 to +1000 °C
NiCr-Ni "K" -200 to +1300 °C
NiCrSi-NiSi "N" -200 to +1300 °C
Fe-CuNi "L" Thermocouple DIN 43710:1985-12 -200 to + 900 °C
Cu-CuNi "U" Thermocouple DIN 43710:1985-12 -200 to +600 °C
Cromel COPEL® "L" GOST R 8.585-2001 -200 to +800 °C
Cromel Alumel® -270 to +1372 °C
W5Re-W20Re "A1" -0 to +2500 °C
W5Re-W26Re "C" ASTM E230M-11: 2011 -0 to +2315 °C