Loading...
4 Configuration parameters
58
Synchronization
time
Configuration
➔ Counter/Integrator
➔ Synchronizat. time
any time
(00:00:00)
Please enter the time at
which the daily, weekly,
monthly or yearly counter/
integrator value is to be
saved.
Period Configuration
➔ Counter/Integrator
➔ Period
1min, 2min, 3min, 4min,
5min, 10min, 15min,
30min, 1h, 2h, 3h, 4h, 6h,
8h, 12h
Only programmable when
the parameter Typ e is set
to “periodic” for at least
one counter/integrator.
The counter/integrator val-
ues are saved at the se-
lected interval.
Ext. operating
signal
Configuration
➔ Counter/Integrator
➔ Ext. operating signal
Logic inp1 — 4,
Logic channel 1 — 6,
Low alarm 1 — 6,
Low comb. al.,
High alarm 1 — 6,
High comb. al.,
Counter/I al. 1 — 6,
C/I comb. alarm,
Comb. alarm,
Memory al.,
Error,
Modbus-Flag
Only programmable when
the parameter Typ e is set
to “external” for at least
one counter/integrator.
Summation of the counter/
integrator values will only
take place if the selected
digital signal is set to “1”.
On a change to “0”, the
values are saved and reset.
Weekday Configuration
➔ Counter/Integrator
➔ Weekday
Monday,
Tuesday,
Wednesday,
Thursday,
Friday,
Saturday,
Sunday
Only programmable when
the parameter Type is set
to “weekly” for at least one
counter/ integrator.
The counter/integrator val-
ues are stored on the
selected day on reaching
the synchronization time.
Daily start time Configuration
➔ Counter/Integrator
➔ Daily start time
any time
(06:00:00)
Only programmable when
the parameter Typ e is set
to “daily from-to” for at
least one counter/integra-
tor.
Daily end time Configuration
➔ Counter/Integrator
➔ Daily end time
any time
(18:00:00)
Only programmable when
the parameter Typ e is set
to “daily from-to” for at
least one counter/
integrator.