Table 19: Router Environmental Specifications
ValueDescription
No performance degradation up to 10,000 ft (3048 m)Altitude
Normal operation ensured in relative humidity range of 5%
through 90%, noncondensing
Relative humidity
•
Normal operation ensured in temperature range of 32°F (0°C)
through 104°F (40°C)
•
Short-term operation ensured in temperature range of 23°
F (–5° C) through 131° F (55° C).
NOTE: As defined in NEBS GR-63-CORE, Issue 4, short-term
events can be up to 96 hours in duration but not more than
15 days per year.
•
Nonoperating storage temperature in shipping container:
–40°F (–40°C) through 158°F (70°C)
Temperature
Designed to meet Telcordia Technologies Zone 4 earthquake
requirements
Seismic
1705 BTU/hour (500 W)Maximum thermal output
NOTE: Install the router only in restricted-access areas, such as dedicated equipment rooms and
equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical
Code, ANSI/NFPA 70.