Table 27 on page 71 lists the power requirements for the fully configured AC-powered routers operating
under typical voltage conditions.
Table 27: MX204 Router AC Router Power Requirements at Typical Temperature (25° C)
Power Requirement
(Watts) with 90%
Efficiency
Power Requirement at 25°
C (Watts)Chassis Configuration
266 W240 WFully configured chassis running at high activity
Table 28 on page 71 lists the power requirements for the fully configured AC-powered routers operating
under maximum voltage conditions.
Table 28: MX204 Router AC Router Power Requirements at Maximum Temperature (55° C)
Power Requirement
(Watts) with 90%
Efficiency
Power Requirement at 55°
C (Watts)Chassis Configuration
311 W280 WFully configured chassis running at high activity
Calculating System Thermal Output
After you have calculated the power consumption for your configuration, you can use that information to
determine the system thermal output (BTUs per hour). To do so, multiply the power consumption in watts
by 3.41.
For example, in Table 27 on page 71 we calculated the power consumption for a fully configured chassis running at
high activity at 25° C typical temperature to be 240 W. Using that information we can calculate the system thermal
output for the configuration:
Power consumption in watts * 3.41 = system thermal output in BTU/hr
240 W * 3.41 = 818.4 BTU/hr
SEE ALSO
MX204 Power System Description | 33
Replacing an MX204 AC Power Supply | 128
AC Power Cord Specifications for MX204 Routers | 40