ACD320 user manual Appendix
- 146-
Feedback value < assigned value -F7.26:the acceleration and deceleration time of output
frequency is set by F0.08/F0.09.
Assigned value-F7.26< feedback value< assigned value- assigned value×F4.26: the
acceleration and deceleration time of output frequency is set by F9.02
F9.03.
Assigned value - assigned value×F4.26< feedback value < assigned value + assigned
value×F4.26:output frequency keep the same basically.
Assigned value + assigned value×F4.26< feedback value < assigned value +F7.26:the
acceleration and deceleration time of output frequency is set by F9.02 and F9.03.
Assigned value +F7.26<feedback value:the acceleration and deceleration time of output
frequency is set by F0.08/F0.09.
3. Macroinstruction set of one driving one constant pressure water supply
Only to set F3.01 =1237, then set F0.12 = 1, the constant pressure water supply application
of macro is effective, parameters are initialized to the factory value in the above form and fine
control led.