ACD320user manual Function parameters list
- 47-
F4.22
Proportional gain
(Kp)
0.00100.00 1.00 119
F4.23 Integral time (Ti) 0.0110.00s 0.10s 120
F4.24
Differential time
(Td)
0.0010.00s 0.00s 121
F4.25
Sampling cycletime
(T)
0.01100.00s 0.10s 122
F4.26
PID control
discrepancy limit
0.0100.0% 0.0% 123
F4.27
Feedback
disconnection
detecting value
0.0100.0% 0.0% 124
F4.28
Feedback
disconnection
detecting time
0.03600.0s 1.0s 125
F4.29 Multi-Speed 0 -100.0100.0% 0.0% 126
F4.30 Multi-Speed 1 -100.0100.0% 0.0% 127
F4.31 Multi-Speed 2 -100.0100.0% 0.0% 128
F4.32 Multi-Speed 3 -100.0100.0% 0.0% 129
F4.33 Multi-Speed 4 -100.0100.0% 0.0% 130
F4.34 Multi-Speed 5 -100.0100.0% 0.0% 131
F4.35 Multi-Speed 6 -100.0100.0% 0.0% 132
F4.36 Multi-Speed 7 -100.0100.0% 0.0% 133
F5 Protection Parameters
F5.00
Motor Overload
Protection Option
0: Noprotection
1: normal motor
2: Variable Frequency motor
1 × 134
F5.01
Motor Overload
Protection Current
20%120.0%(motor rated current) 100.0% 135
F5.02
Power-down
Frequency Drop
Point
70.0110.0%standard bus voltage 80.0% 136
F5.03
Instant power-down
Frequency drop rate
0.00HzF0.04 0.00Hz 137
F5.04
Over-voltage Stall
Protection
0: prohibit
1: allow
0 138
F5.05
Over-voltage Stall
Protection Voltage
110150%380V 120%
139
110150%220V 115%
F5.06 Over-curent stall 80200% 160% 140

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the K&R ACD320 Series and is the answer not in the manual?

K&R ACD320 Series Specifications

General IconGeneral
BrandK&R
ModelACD320 Series
CategoryInverter
LanguageEnglish