ACD320user manual Function parameters list
- 50-
detection delay
Function
Code
Name Set range
Default
Value
Modifi
cation
Serial
No
F7.26
PID adjustable
range
050.0 10.0 175
F7.27
Operation when set
frequency is lower
than low limit
frequency
0:Run at lower limit Freq.
1:Run at 0Hz.
0 176
F7.28
Selcet sleeping
signal
0: Select internal sleeping signal
1: Select external sleeping signal
2: Internal and external signal are valid at the same
time.
0 177
F7.29
Simple PLC
running mode
1: Run circularly.
2: Stop after running for one circulation.
3: Run at the selected speed after running for one
circulation.
1 178
F7.30
The 0
st
step
running time.
0999.9 0 179
F7.31
The 1
st
step
running time.
0999.9 0 180
F7.32
The 2
nd
step
running time.
0999.9 0 181
F7.33
The 3
rd
step running time.
0999.9 0 182
F7.34
The 4
th
step
running time.
0999.9 0 183
F7.35
The 5
th
step
running time.
0999.9 0 184
F7.36
The 6
th
step
running time.
0999.9 0 185
F7.37
The 7
th
step
running time.
0999.9 0 186
F7.38
Simple PLC
selection record or
not when power
off.
0: Record when power off
1: No record when power off.
0 187
F7.39
Simple PLC
running time unit.
0:s
1:min
0 188
F7.40 Failure shield
BIT0: Module protection shield
0:Invalid 1: Valid
1
0 × 189
BIT1: Soft overcurrent shield.
0:Invalid 1: Valid
2
BIT2: Over-voltage shield.
0:Invalid 1: Valid
4