System operation
Mode AI 3 φ (change by analog input):
With the setting AI 3 φ (change by analog input), the target cos-phi is determined by
means of a congurable curve. The parameters refer to 100% of the analog input (10V
or 20mA). At the AI module, the channel can be set to voltage input (0–10V) or current
input (0–20mA) with DIL switches. The range adaption is made using the parameter AI
2-10V. When AI 2-10 NO is set, the range is 0–20mA or 0–10V.
Cos-phi2 (power recovery) has no function in this mode.
The cos-phi1 (power consumption) is used for the baseline between the adaption ramps.
A hysteresis can be programmed using the hyst. parameter.
The transition to the new target cos-phi can be attenuated using the “t-delay” parameter.
Cosphi1 1.00
Mode AI 3φ
t-delay 000 seconds
Q-Control No
cosφ A 0.90 ind.
from (%) 0%
to (%) 50%
cosφ B 0.90 cap.
from (%) 50%
to (%) 100%
AI 2-10 V NO
Hysteresis 9.00%
Function:
With an input voltage of 0V (= 0%) the instantaneous target-cosφ would be 0.95 ind.
With an input voltage of 5V (= 50%) the instantaneous target-cosφ would be 1.0.
With an input voltage of 10V (= 50%) the instantaneous target-cosφ would be 0.95 cap.