336
Errata
Section 6.2: LI03 = B(Level - Inspection - Correction), NUM = 3, changed to Decode
with LI16.
Section 6.2: Main Contactor Check output function signaling and connection correct;
output turns on at Direction + Speed, not Direction + Enable and enable should be
connected to NC contact, not NO.
Section 6.2: Main Contactor Control input function wiring corrected; input should
come from NC contact, not NO contact. Section 6.2: Main Contactor Output + Input
wiring diagram updated.
Section 6.4: LE35 selections changed.
Section 6.6: ETS prole rates changed to LS33-35 One Floor from LS48-49 ESD
rates; NTS prole rates changed to LS48-49 NTS/ETS rates from LS33-35 One Flloor.
Section 6.9: Timing Diagram updated; LT02 and LT12 timers.
Section 6.11: LX17, 19, 20 description changed from ETS to NTS.
Section 6.14: Timing Diagram updated; LT02 and LT12 timers.
Section 6.14: Main Contactor Control signaling description corrected; output turns
on at Direction + Speed, not Direction + Enable.
Section 6.14: Cabinet Fan On heatsink temperature output condition changed from
45 to 40 degrees Celsius.