EasyManuals Logo

Lamtec F300K Series User Manual

Lamtec F300K Series
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
39
6 Commissioning
Set the Weightings Between UV and IR Signals (Dual Sensor)
Switch to the menu .
Fig. 6-8 Call up the weighting menu
The amplitude bars would be displayed; UV from the menu IR from the menu and the
weighted signals . The percentage value of the amplitude bars gives a relative amount of the
individual signals to the weighted signals.
Fig. 6-9 Weightings Menu
Settings of F300K Weightings
1. In the weightings menu, you can adjust the settings so that the individual signals UV and
IR can be added with the required percentage and be processed further.
a) Control with , to increase the percentage of UV signal to the weighted signal.
b) Control with , to decrease the percentage of UV signal to the weighted signal.
2. Control with to confirm the weightings. A countdown of 8 s starts now. This would be
shown with blinking. During the countdown, you must confirm the settings through ,
otherwise you will get an error message and the settings will not be saved
Alternatively you can discard the process with
WARNING!
The shut-off parameters which are determined by the settings procedure are only valid when
these are verified through corresponding shut-off tests, see chapter6.4.5 Switch-off Test

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec F300K Series and is the answer not in the manual?

Lamtec F300K Series Specifications

General IconGeneral
BrandLamtec
ModelF300K Series
CategoryScanner
LanguageEnglish